Local Law 152 requires most NYC buildings with gas piping to have it inspected every four years by a NYC Licensed Master Plumber, or by a trained journeyman plumber working under one. Your due year depends on your building's community district, and the certification must be filed in DOB NOW: Safety. One- and two-family homes are exempt. Nationwide Plumbers (NYC Licensed Master Plumber #2023, Anthony Garofalo) inspects, prepares the filing and corrects any conditions the inspection finds.
Got a letter or notice about Local Law 152?
- Check the due year for your building's community district in the table below. Inspections repeat every four years.
- If your building failed an inspection or has a violation, read what happens after a failed inspection.
- If you think the building is exempt, read is my building exempt from Local Law 152.
- Call 718-748-2727 to schedule. We check your address and confirm your due year first.
"We hired Nationwide Plumbers to do an LL152 gas line inspection. Good communication, prompt service and great price!"
James S., November 2026, Google review
Local Law 152: the short answers
What is Local Law 152?
Local Law 152 of 2016 is the New York City law that requires periodic inspections of building gas piping. Most buildings with gas piping must have it inspected every four years, and the certification is filed with the Department of Buildings in DOB NOW: Safety. What the inspection involves.
Who can perform a Local Law 152 inspection?
Only a NYC Licensed Master Plumber, or a DOB-registered journeyman plumber with at least 7 hours of DOB-accepted gas inspection training who works under the direct and continuing supervision of one. An engineer or architect cannot perform the inspection. Who can perform the inspection.
Is my building exempt from Local Law 152?
One- and two-family homes and other buildings in occupancy group R-3 are exempt. A building with no gas piping is not exempt from filing: it files a one-time certification that it has no gas piping. New buildings are not exempt either: with a first certificate of occupancy dated on or after December 6, 2016, the first filing is due in the building's 10th year. Does your building need an inspection?
When is my Local Law 152 inspection due?
Every four years, by December 31 of the year set by your building's community district. Districts 4, 6, 8, 9 and 16 are due in 2026. Districts 11, 12, 14, 15 and 17 are due in 2027. Districts 1, 3 and 10 are due in 2028. Districts 2, 5, 7, 13 and 18 are due in 2029. Find your due year.
What a Local Law 152 inspection involves
An LL152 inspection is a visual inspection and gas leak survey of the building's gas piping, done on site by a qualified plumber. Local Law 142 of 2025 set the scope from the point where gas piping enters the building through the point of connection to gas appliances. In practice the plumber covers:
- Exposed gas piping in common areas: the meter room, cellar, boiler and mechanical rooms, hallways, corridors, public spaces and the roof where piping runs there.
- Exposed gas piping and gas appliances in commercial and other non-residential tenant spaces.
- A leak survey with a combustible gas detector everywhere the visual inspection applies, including the presumed path of piping that is not exposed.
- Atmospheric corrosion and deterioration of the piping.
- Illegal connections, non-code-compliant installations and improper use of the gas piping.
Gas piping, appliances and connections inside dwelling units (apartments) are not part of the inspection. If the plumber cannot reach every required area, the inspection cannot be certified as complete and has to be repeated, so plan access before the visit.

Need your building inspected? Call Nationwide Plumbers at 718-748-2727 or request a time online.Call 718-748-2727
Does your building need an LL152 inspection?
LL152 applies to all buildings except one- and two-family homes and other buildings in occupancy group R-3. DOB lists the Department of Finance building classes that do not need to comply: A0 to A9, B1, B2, B3, B9, CM, M3 (with 2 or fewer permanent dwelling units), M4 (with 20 or fewer occupants), N2, S0, S1, S2 and V. Most multifamily, mixed-use, co-op, condo and commercial buildings must comply.
- Check your address first. DOB publishes an LL152 lookup by address (in DOB NOW, under Additional Tools) and a spreadsheet of every covered property. If your building class is wrong, the fix goes through the Department of Finance.
- Each building on a lot files separately. A rear building or garage with its own BIN needs its own filing.
- New buildings. A building with a first certificate of occupancy dated on or after December 6, 2016 files in its 10th year, then again in its community district's next due year.
- No gas piping at all. A Licensed Master Plumber or a registered design professional certifies once that the building has no gas piping.
- Gas piping but no active gas service. This is filed with documentation from the utility and the owner, and it is filed again every four years.
Not sure where your building falls? Read our guide Is my building exempt from Local Law 152?
When is your building due?
The due year comes from your building's community district number, which is the same in every borough. Find the district by searching your address on the NYC Department of City Planning community profiles, then match it below. The certification is due by December 31 of that year.
| Sub-cycle | Community districts | Cycle 2 due by | Cycle 3 due by |
|---|---|---|---|
| A | 1, 3, 10 | Dec 31, 2024 | Dec 31, 2028 |
| B | 2, 5, 7, 13, 18 | Dec 31, 2025 | Dec 31, 2029 |
| C | 4, 6, 8, 9, 16 | Dec 31, 2026 | Dec 31, 2030 |
| D | 11, 12, 14, 15, 17 | Dec 31, 2027 | Dec 31, 2031 |
The inspection can happen any time during your due year. If you cannot get it done in time, the owner can request a one-time 180-day extension in DOB NOW: Safety, filed by the same December 31 deadline. Source: NYC Department of Buildings.
Who can perform the inspection
Under DOB's rule (1 RCNY 103-10), only two kinds of people can inspect:
- A NYC Licensed Master Plumber (LMP).
- A journeyman plumber working under the direct and continuing supervision of an LMP, who holds a DOB journeyman plumber registration and has completed a DOB-accepted gas piping inspection course of at least 7 classroom hours.
Either way, the Licensed Master Plumber takes responsibility for the inspection and attests to it. A registered design professional (engineer or architect) cannot perform an LL152 inspection, but can certify that a building has no gas piping. Before you hire anyone, DOB recommends checking the license with its License Search tool. Our inspections are performed under NYC Licensed Master Plumber #2023, held by Anthony Garofalo.
Inspection, certification, submission and correction
These four words get mixed up. They are separate steps with separate deadlines, and since July 27, 2026 all of them are handled in DOB NOW: Safety. The paper GPS1 report and GPS2 certification forms are no longer used.
| Step | Who | Deadline |
|---|---|---|
| Inspection notice: the inspection is scheduled with DOB, which may send an inspector to audit it | The LMP or journeyman | At least two days before the inspection |
| Inspection: visual inspection and leak survey on site | LMP or qualified journeyman | Any time in your due year |
| Results to the owner: the inspection results are entered for the owner | The inspecting LMP | Within 30 days of the inspection |
| Initial certification submitted: the owner attests with an NYC.ID account and pays the DOB filing fee | Owner and LMP both attest | Within 60 days of the inspection, and by December 31 of the due year |
| Unsafe conditions: reported at once to the owner, the gas utility and DOB | The inspecting LMP | Immediately |
| Correction and certification of correction: conditions are fixed under the Construction Codes, with permits where required | Owner hires an LMP; the LMP certifies | Within 120 days of the inspection, or 180 days if the initial certification said more time was needed |
A few points owners often miss. The LMP cannot attest on the owner's behalf; a representative of the owner entity has to log in and attest. If conditions are listed on the initial certification, a separate certification of correction is required even if the work is done quickly. Missing the filing deadline brings a DOB civil penalty of $5,000 per building, or $1,500 for a 3-family building, and paying the penalty does not replace the inspection and filing. If the inspection finds conditions to correct, see what happens after a failed LL152 inspection.
How we handle your LL152 inspection
- Confirm the requirement. We check your address and BINs in DOB's LL152 lookup and confirm your due year.
- Schedule and notify DOB. We set a date with your super or manager and file the inspection notice in DOB NOW: Safety.
- Inspect. We inspect every required area and run the leak survey.
- Prepare the filing. We enter the results in DOB NOW: Safety. You log in, attest and pay the DOB filing fee, and the certification is submitted.
- Correct what we find. If conditions need correction, you get a written quote before any work starts. We pull the permits, make the repairs, coordinate with the utility if the gas was shut off and file the certification of correction.
Boards and managing agents can read our Local Law 152 guide for co-op and condo boards. For a full plain-English overview of the law, see Local Law 152 gas inspections: what NYC owners must know.
What LL152 is not
- It is not your utility's service line inspection. Con Edison and National Grid inspect their own meters and service lines and schedule those visits themselves. That does not satisfy LL152.
- It is not a gas detector requirement. Natural gas detectors in apartments fall under a separate NYC rule. An LL152 inspection does not install or certify detectors.
- It is not an emergency response. If you smell gas, leave the building and call 911 or your gas utility from outside. National Grid: 718-643-4050. Con Edison: 1-800-752-6633.
Ready to schedule your Local Law 152 inspection? Call 718-748-2727 or request a time below.Call 718-748-2727
Local Law 152 inspections: FAQ
Who can perform a Local Law 152 inspection?
A NYC Licensed Master Plumber, or a DOB-registered journeyman plumber who has completed a DOB-accepted gas inspection course of at least 7 hours and works under the direct and continuing supervision of a Licensed Master Plumber. The Licensed Master Plumber attests to the inspection either way.
How often is the inspection required, and when is my building due?
Every four years. The due year comes from the building's community district: districts 1, 3 and 10 are due in 2028; 2, 5, 7, 13 and 18 in 2029; 4, 6, 8, 9 and 16 in 2026 and 2030; 11, 12, 14, 15 and 17 in 2027 and 2031. The certification is due by December 31 of that year.
Is my building exempt?
One- and two-family homes and other buildings in occupancy group R-3 are exempt, along with the Department of Finance building classes DOB lists. A building with no gas piping still files a one-time certification of no gas piping. Check your address in DOB's LL152 lookup to confirm.
What replaced the GPS1 and GPS2 forms?
Since July 27, 2026, LL152 inspections, certifications, corrections and extension requests are filed in DOB NOW: Safety. The paper GPS1 report and GPS2 certification are no longer required or accepted. The owner must attest in DOB NOW and pay the DOB filing fee.
What happens if the inspection finds problems?
Unsafe conditions are reported immediately to the owner, the gas utility and DOB and must be corrected right away. Other listed conditions must be corrected and a certification of correction filed within 120 days of the inspection, or 180 days if the initial certification said more time was needed.
What is the penalty for missing the deadline?
Under 1 RCNY 103-10, an owner who does not file the certification on time is liable for a civil penalty of $5,000, or $1,500 for a 3-family building. Paying the penalty does not replace the inspection and filing.
Can I get more time?
Yes, once. The owner can request a one-time 180-day extension in DOB NOW: Safety, filed by the December 31 deadline. The inspection and certification must be completed before the extension ends.
Managing a building or portfolio? See plumbing for property managers for inspection coordination, COIs on request, net 30 management accounts and emergency dispatch.